Kaiflex KK+ solukumi

 

   KKplus      

Kaiflex KKplus - PRODUCT DESCRIPTION

Highly flexible, closed-cell insulation material based on elastomeric foam defined by an extremely high water vapour resistance factor and an extremely low thermal conductivity.

Materiaali:

Highly flexible, closed-cell insulation, FEF (Flexible Elastomeric Foam)

Kuvaus:

Highly flexible, closed-cell insulation material defined by an extremely high water vapour resistance factor and an extremely low thermal conductivity.

Käyttöalueet:

For condensation prevention and energy loss limitation where pips and ducts, chillers and air conditioning equipment are required.

Temperature range  
Ylin sallittu lämpötila:

+105°C (sheets +85°C)

 

Alin sallittu lämpötila:

-50°C (-200°C)

 

Please, contact the Kaimann Technical Services Department for temperatures exceed -50°C.

Lämmön johtavuus λ DIN EN ISO 8497 / DIN EN 12667  
Medium temperature °C
    - 30 - 20   0   + 10 + 20 + 40   + 70
   
   

Installation

Adhesive 414
Tube Sheet
Kaifinish
Cleaner

Technical

Accessories
Tube Sheet

Ship

Test Report IMO
Test Report Lloyd's Register
Test Report Sea BG
Test Report Modul B Sea BG
Test Report Det Norske Veritas

Certificates

DIN CERTCO Conformity Tube
DIN CERTCO Conformity Sheet

Safety      

Adhesive 414
Cleaner
Tube Sheet SD
Kaifinish

Katso myös
Solukumi
Solukumieriste
Solumuovi

      

Lämmön johtavuus W(m•K)
0,030 0,031 0,033 0,034 0,035 0,037 0,040
 
Vesihöyryn läpäisevyys DIN EN 13469 / DIN EN 12068 Höyrydiffuusiovastuskerroin:

≥ 10.000 µ

Paloluokitus DIN EN 13501  
Letkut

highly flame retardant, BL-s3, d0, ≤ 25 mm  thickness, ABZ-No.: Z-56.269-3498

 

 

Levyt

highly flame retardant, B-s3, d0, 10 mm to 32 mm thickness, ABZ-No.: Z-56.269-3497

 

self extinguishing, does not propagate fire and produces no burning droplets in a fire situation

 

Korroosion esto:

Kaiflex KK plus complies with DIN 1988 part 7

AGI eristeen viite no:t  
Letkut

36.12.01.06.04

Levyt

36.01.01.02.04

Tuotantoprosessi:

free of CFC, HFCKW, Formaldehyde, Cadmium

All technical information stated in the above list is based on test results obtained under typical conditions. You are adviced to check with the Kaimann Technical Department whether the given information is appropriate for the specific use intended by the recipient.